B: Modbus Map and Retrieving Logs
Doc# E149701 MM-22
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
4E2B - 4E2B 20012 - 20012 Reset Option Card 1 Input Accumulators UINT16 password (Note 5) 1
4E2C - 4E2C 20013 - 20013 Reset Option Card 1 Output Accumulators UINT16 password (Note 5) 1
4E2D - 4E2D 20014 - 20014 Reset Option Card 2 Input Accumulators UINT16 password (Note 5) 1
4E2E - 4E2E 20015 - 20015 Reset Option Card 2 Output Accumulators UINT16 password (Note 5) 1
Block Size: 16
conditional write
5207 - 5207 21000 - 21000 Initiate Meter Firmware Reprogramming UINT16 password (Note 5) 1
5208 - 5208 21001 - 21001 Force Meter Restart UINT16 password (Note 5) causes a watchdog reset, always reads 0 1
5209 - 5209 21002 - 21002 Open Privileged Command Session UINT16 password (Note 5) meter will process command registers (this register
through 'Close Privileged Command Session' register
below) for 5 minutes or until the session is closed,
whichever comes first.
1
520A - 520A 21003 - 21003 Initiate Programmable Settings Update UINT16 password (Note 5) meter enters PS update mode 1
520B - 520B 21004 - 21004 Calculate Programmable Settings Checksum
(Note 3)
UINT16 0000 to 9999 meter calculates checksum on RAM copy of PS block 1
520C - 520C 21005 - 21005 Programmable Settings Checksum (Note 3) UINT16 0000 to 9999 read/write checksum register; PS block saved in
nonvolatile memory on write (Note 8)
1
520D - 520D 21006 - 21006 Write New Password (Note 3) UINT16 0000 to 9999 write-only register; always reads zero 1
520E - 520E 21007 - 21007 Terminate Programmable Settings Update (Note
3)
UINT16 any value meter leaves PS update mode via reset 1
520F - 5211 21008 - 21010 Set Meter Clock TSTAMP 1Jan2000 - 31Dec2099 1 sec saved only when 3rd register is written 3
5212 - 5212 21011 - 21011 Manually Trigger Waveform Capture UINT16 any value applies to Shark 300 only; returns busy exception if
blocked by another capture in progress
1
5213 - 5219 21012 - 21018 Reserved Reserved 7
521A - 521A 21019 - 21019 Close Privileged Command Session UINT16 any value ends an open command session 1
Block Size: 20
read/write
658F - 659A 26000 - 26011 Perform a Secure Operation UINT16 encrypted command to read password or change meter
type
12
Block Size: 12
write only in PS update mode
752F - 752F 30000 - 30000 CT multiplier & denominator UINT16 bit-mapped
dddddddd mmmmmmmm
high byte is denominator (1 or 5, read-only),
low byte is multiplier (1, 10, or 100)
1
7530 - 7530 30001 - 30001 CT numerator UINT16 1 to 9999 none 1
7531 - 7531 30002 - 30002 PT numerator UINT16 1 to 9999 none 1
7532 - 7532 30003 - 30003 PT denominator UINT16 1 to 9999 none 1
7533 - 7533 30004 - 30004 PT multiplier & hookup UINT16 bit-mapped
mmmmmmmm mmmmhhhh
mm…mm = PT multiplier (1, 10, 100, or 1000)
hhhh = hookup enumeration (0 = 3 element wye[9S], 1 =
delta 2 CTs[5S], 3 = 2.5 element wye[6S])
1
Encryption Block
Programmable Settings Section
Basic Setups Block
Privileged Commands Block
Vue de la page 221
1 2 ... 217 218 219 220 221 222 223 224 225 226 227 ... 297 298

Commentaires sur ces manuels

Pas de commentaire

Bloomfield Accesorios Para Hacer Café manuales de usuario

Empezando en S

Haga clic en el alfabeto a continuación para desplazarse a la lista completa de modelos que comienzan con esa letra

Modelos Tipo de documento
SS2 Series
Especificaciones   Bloomfield SS2 Series Specifications, 26 paginas